BFI-H2-32-0180-3F1X-TN
Article number 62157
- Output power 4,0 kW
- Output 3x230 VAC, 18 A
- Input voltage 3x200-240 VAC
- IP66
Facts
General description
Article number | 62157 |
Mechanical
IP class | IP66 |
Physical size | Size 3 |
Measurements (H x W x D) | 310 mm x 211 mm x 273 mm |
Weight | 8.5 kg |
Typical power loss at rated power | 0,02 |
Main switch | No |
Built in Main switch, control switch and potentiometer | No |
Conformal coated PCBs | No |
Output ratings
Output voltage | 3 x 230 VAC |
Rated motor current | 18 A |
Overload capacity | 110% for 60 seconds, 125% for 3 seconds |
Motor power | 4,0 kW |
Output frequency | 0 – 120Hz, 0.1Hz resolution |
Supported motor types | 3 phase AC induction (IM) |
Built-in brake transistor | No |
Regenerative capacity | No brake transistor |
Input ratings
Supply voltage | 200 – 240VAC ± 10% |
Voltage fluctuations | +/- 10% |
Phase imbalance | 3% maximum allowed |
Displacement factor | > 0.98 |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Total harmonic current distorsion | No |
Control specification
Control modes | V/F Voltage Vector, Energy Optimised V/F |
Current/torque limitation | Current limitation |
PWM frequency | 4-32 kHz effective |
Stopping mode | Ramp to Stop: User Adjustable 0.1 – 600 seconds,Coast to Stop |
Braking | No |
Skip frequency | Yes |
Analog setpoint control | 0 to 10V, 10 to 0V, −10 to 10V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
Digital setpoint control | 8 fixed speeds, Motorised Potentiometer, Internal PLC, Keypad, Modbus RTU, CANopen, Optional: PROFIBUS DP, DeviceNet, EtherNet/IP, EtherCat, PROFINET, Modbus TCP, CC-Link |
Communication
Modbus RTU | 9.6 - 115.2 kbps selectable (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | Built-in |
Modbus TCP | Yes, external option |
Ethernet IP | Yes, external option |
EtherCat | Yes, external option |
Profinet IO | Yes, external option |
Profibus DP(DPV1) | Yes, external option |
Device Net | Yes, external option |
CC-Link | Yes, external option |
CAN open | No |
Display
Programmable display | Yes |
Multi language OLED display | Yes |
External OLED display | Yes |
LED display | No |
HVAC
PID-control | Yes with sleep/wake up functionality |
Spin start | Yes |
Pump dry protection | Yes |
Pump prime and burst protection | Yes |
Stir function | Yes |
Motor pre-heat | Yes |
Broken impeller and broken belt detection | Yes |
Automatic cleaning for pumps | Yes |
Bypass control | Yes |
Fire mode | Yes |
Control terminals
Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
Inputs | 5 in total, 3 Digital, 2 Analog or Digital, selectable |
Digital inputs | 10-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Outputs | 4 total, 2 relays, 2 analog or digital |
Digital transistor outputs | 24VDC/20 mA, Internal supply |
Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 6A AC, 5A DC |
Analog outputs | 0 to 10 Volt, 0 to 20mA, 4 to 20mA |
Safety inputs | 2 |
Extra IOs | Yes, internal option |
Control features
Speed control Master/slave | Yes, Master and slave |
Modbus master functionality | Yes, Master and slave |
Advanced hoist control | No |
Built-in PLC | Yes |
Standard compliances
Low voltage directive | Adjustable speed electrical power drive systems. EMC requirements |
EMC directive | 2004/108/EC, Cat C2 according to EN61800-3:2004 |
Conformance | CE, UL |
Machine directive | 2006/42/EC |
Marine approvals | DNV-GL |
Safe torque OFF | Cat 3/PL"d" According to ISO 13849-1, SIL CL 2 According to EN61800-5-2 / EN62061 / IEC61508 |
Restriction of hazardous substances | RoHS2 |
Registration evaluation and authorisation of chemicals | Reach |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
DC Bus discharge time | EN 61800-5-1:2007 |
Electrostatic discharge | EN 61800-3:2004+A1-2012. Test techniques EN 61000-4-2:2009. |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Electrical fast transient burst | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-4:2004. |
Ambient conditions
Temperature operation | -10 to 40 °C |
Humidity | 95% max, non-condensing |
Maintenance
Fault memory | Last 4 Trips stored with time stamp |
Data logging | Logging of data prior to trip, Current, Temperature, DC Bus Voltage |
Maintenence indicator | Yes. Onboard service life monitoring |
Monitoring | Hours Run Meter, kWh/MWh meter |
Resources
Limited availability
BFI-H2-32-0180-3F1X-TN
Article number 62157
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: