Facts
General description
| Article number | 100-8227 |
| Warranty | Up to 2 years |
| Article status | Active |
| Shock operating | IEC 60068-2-27 (15G) |
| Vibration resistence | Sine vibration (based on IEC 60068-2-6), DNVGL-CG-0339 (Vibration Class B, 4G) |
| Industrial emissions | EN 61000-6-4/2019 |
| Industrial immunity | EN 61000-6-2 : 2019 |
| Installation position | Horisontal, Vertical |
| Power dissipation | 35 mA maximum @ 5.0 VDC |
| Isolation | I/O to Logic : Photocoupler isolation |
| Field power | Supply voltage : 24 VDC Nominal (AC Power Not used), Voltage range : 22V ~ 26 VDC. Power dissipation: 20 mA maximum @ 24 VDC |
| Weight | 72g |
| Module size | 12 x 110 x 75 mm |
Certifications
| General | CE, FCC, UL, cUL |
| Hazardous | UL C1D2 |
| Marine | DNV GL |
| Safety | UL508, CAN/CSA C22.2 No.142-M1987 |
Environmental
| Mounting | 35mm DIN rail |
| Operating temperature | -25 ~ 60℃ |
| Storage temperature | -40 ~ 85℃ |
| UL temperature | -25 ~ 60℃ |
| Relative humidity | 5 ~ 90% non-condensing |
Digital output module specifications
| Indicators | 4 Green output state |
| Outputs per module | 4 Points, Bi-directional |
| Output voltage range | Max. 24 VDC @ 2.0A resistive, Max. 240 VAC @ 2.0A resistive |
| ON state voltage | 0.5V @ 2.0A, Resistive Load, 24 VDC |
| Relay type | Form C, Single Pole double Throw (SPDT) |
| Frequencey range | 47 ~ 63Hz |
| Expected contact life | Min. 5M Cycles (Resistive) |
| Common type | 1 Commons per 1 points (Total 4 Commons) |
Resources
Manuals
| File name | Date | |
|---|---|---|
| M2774 M-Series Digital output | 2022-09-06 11:38:48 | |
| M-Series Common User Guide & Hotswap functionality | 2022-09-06 14:15:24 |
Knowledge
| File name | Date | |
|---|---|---|
| Common noise filter NBH-06-432-D to FnIO S- and M-series (for DNV certificate) | 2022-09-06 11:36:38 | |
| FnIO M-, G- and S-series Serial number and Production date | 2023-07-20 11:30:16 | |
| Always add a power module (M7001/7002) after the network adapter | 2023-08-09 15:20:30 | |
| Shock resistance of G- and M-series (IEC 60068-2-27) | 2022-09-06 14:16:00 | |
| How to download Free software packages from SmartStore | 2025-05-08 10:17:08 |
Product information
| File name | Date | |
|---|---|---|
| Conversion guide for alternative products between S-series remote IO to G- or M-series | 2022-09-06 11:38:29 |
Certificates
| File name | Date | |
|---|---|---|
| UL & cUL Certificate of compliance - Beijer M-series | 2022-11-11 08:37:00 | |
| UL-HAZLOC Certificate of compliance - Beijer M-series | 2022-11-11 08:37:24 | |
| DNV GL - Type Approval Certificate - Beijer M-series | 2025-01-10 15:21:18 | |
| Beijer M-series certificate overview | 2025-01-29 09:11:22 | |
| ATEX Zone 2 Certificate - Beijer FnIO M-series | 2022-11-15 08:20:20 | |
| CE DoC - Beijer M-series including EMC, LVD, RoHS-II & Reach | 2025-01-13 09:01:11 | |
| FCC DoC - Beijer M-series | 2022-11-11 08:35:14 |
Information document
| File name | Date | |
|---|---|---|
| Beijer M-series Caution and Warning (ATEX & RoHS) Rev.3.02 | 2022-11-11 08:55:42 |
Software
| File name | Date | |
|---|---|---|
| IOGuide2(Beijer)-v2.0.0.0 [TEST version] | 2025-11-06 15:27:32 |
Drawings
| File name | Date | |
|---|---|---|
| M- and ML-series Drawing, 2D CAD files #5 (Electrical) | 2025-04-30 09:08:04 | |
| M- and ML-series Drawing, 3D / 2D CAD files (Mechanical) | 2025-04-30 09:06:35 |
Limited or Unavailable
M2774
4 digital outputs Relay
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: